Technical Notes
Calculating the Pressure Drop of Runtal Radiators
Calculating the pressure drop for Runtal radiators is a simple process, if you keep the following facts in mind:
1. Do not have a flow of more than 1.5 GPM in any one tube of the radiator.
2. Virtually all of the pressure drop in a Runtal radiator occurs in getting the flow of water in and out of the headers at each end of the radiator. There is almost no pressure drop in the tubes between the headers. Therefore, a long radiator and a short radiator (with the same water flow) would have virtually the same pressure drop.
3. The pressure drops shown in the Runtal Pressure Drop Charts are per radiator, NOT per foot of radiator.
4. The total pressure drop is a combination of two components, the radiator pressure drop plus the pressure drop of the pipe connections.
5. There are 0.0244 gallons/tube per foot of radiator.
6. The pressure drops of type RS2 radiators are difficult to calculate. Contact your Runtal representative and Runtal personnel will calculate the pressure drops of RS2 radiators.
Example #1
R-4 Radiator @ 10'-0" with a 170۫ F average water temperature and a 20۫ F temperature drop.
|
½” type “A” pipe connections. |
Capacity = 507 BTUH/FT x 10 FT = 5070 BTUH
|
GPM |
= |
Capacity |
= |
5070 |
| |
|
(500) x Temp. Drop |
|
(500) x (20) |
GPM = 0.507 gpm |

From page # TR-50, using 0.507 gpm, the pressure drop is:
|
0.01 FOH/radiator x (1) radiator = 0.01 FOH
0.01 FOH/pipe conn. x (2) pipe conn. = 0.02 FOH
Total for the R-4 Radiator = 0.03 FOH |
Example #2
R-4 Radiator @ 10’-0” with a 170۫ F average water
temperature and a 20۫ F temperature drop.
|
½” type “C” pipe connections. |
Capacity = 507 BTUH/FT x 10 FT
= 5070 BTUH
|
GPM |
= |
Capacity |
= |
5070 |
| |
|
(500) x Temp. Drop |
|
(500) x (20) |
GPM = 0.507 gpm |

From page # TR-60, using 0.507 gpm, the pressure drop is:
|
0.05
FOH/radiator x (1) radiator = 0.05 FOH
0.01 FOH/pipe conn. x (2) pipe conn. = 0.02
FOH
Total for the R-4 Radiator = 0.07 FOH |
Example #3
(3) R-4 Radiators @ 10’, 8’, and 12’ in an opposite end
series of radiators, 170۫ F average water temperature and a
20۫ F temperature drop. ¾” type “B” pipe connections.
Capacity = 844 BTUH/FT x (10 + 8 + 12) = 25320 BTUH
|
GPM |
= |
Capacity |
= |
25320 |
= |
2.53
gpm |
| |
|
(500) x Temp. Drop |
|
(500)
x (20) |
|
|

From TRF-50, using 2.53 gpm, the pressure drop for the three
radiators is:
|
0.32
FOH/radiator x (3) radiators = 0.96 FOH
0.08 FOH/pipe conn. x (6) pipe conn. = 0.48 FOH
Total for the 3-Radiator Series = 1.44 FOH |
Example #4
(3) R-4 Radiators @ 10’, 8’, and 12’ in a same-end series of
radiators, 170۫ F average water temperature and a 20۫ F
temperature drop. ¾” type “C” pipe connections.
Capacity = 844 BTUH/FT x (10 + 8 + 12) = 25320 BTUH
|
GPM |
= |
Capacity |
= |
25320 |
= |
2.53
gpm |
| |
|
(500) x Temp. Drop |
|
(500)
x (20) |
|
|

From TRF-60, using 2.53 gpm, the pressure drop for the
3-radiator same-end series is:
|
1.21
FOH/radiator x (3) radiators = 3.63 FOH
0.08 FOH/pipe conn. x (10) pipe conn. = 0.8 FOH
Total for the 3-Radiator Series = 4.43 FOH |
Model Type R
Pressure Drop: Opposite End
RADIATOR PRESSURE DROP - FOOT OF HEAD PER RADIATOR

| |
RADIATOR MODEL
NUMBER OF TUBES
FOR FLOW |
CONNECTION PD
PER CONNECTION |
|
STD
PRESSURE
TUBE |
R-1 |
R-2 |
R-3 |
R-4 |
R-5 |
R-6 |
R-7 |
R-8 |
R-9 |
R-10 |
1/2"
CONN
PD |
3/4"
CONN
PD |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| → |
0.05 |
0.21 |
0.05 |
0.02 |
0.01 |
0.01 |
0.01 |
0.00 |
0.00 |
0.00 |
0.00 |
0.01 |
0.01 |
| |
0.75 |
0.45 |
0.12 |
0.05 |
0.03 |
0.02 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.03 |
0.01 |
| |
1.00 |
0.79 |
0.21 |
0.09 |
0.05 |
0.04 |
0.02 |
0.02 |
0.01 |
0.01 |
0.01 |
0.04 |
0.03 |
| |
1.50 |
1.72 |
0.45 |
0.21 |
0.12 |
0.08 |
0.05 |
0.04 |
0.03 |
0.02 |
0.02 |
0.09 |
0.04 |
| |
2.00 |
3.00 |
0.79 |
0.36 |
0.21 |
0.13 |
0.09 |
0.07 |
0.05 |
0.04 |
0.04 |
0.18 |
0.06 |
| |
2.50 |
4.61 |
1.21 |
0.55 |
0.32 |
0.21 |
0.15 |
0.11 |
0.08 |
0.07 |
0.05 |
0.25 |
0.08 |
| |
3.00 |
6.56 |
1.72 |
0.79 |
0.45 |
0.29 |
0.21 |
0.15 |
0.12 |
0.09 |
0.08 |
0.35 |
0.10 |
| |
3.50 |
8.83 |
2.32 |
1.06 |
0.61 |
0.40 |
0.28 |
0.21 |
0.16 |
0.13 |
0.10 |
0.44 |
0.15 |
|
GPM |
4.00 |
11.42 |
3.00 |
1.37 |
0.79 |
0.51 |
0.36 |
0.27 |
0.21 |
0.16 |
0.13 |
0.56 |
0.18 |
| |
4.50 |
14.34 |
3.76 |
1.72 |
0.99 |
0.64 |
0.45 |
0.34 |
0.26 |
0.21 |
0.17 |
0.63 |
0.20 |
| |
5.00 |
17.57 |
4.61 |
2.11 |
1.21 |
0.79 |
0.55 |
0.41 |
0.32 |
0.25 |
0.21 |
0.80 |
0.25 |
| |
5.50 |
21.12 |
5.54 |
2.53 |
1.45 |
0.95 |
0.67 |
0.49 |
0.38 |
0.30 |
0.25 |
1.00 |
0.28 |
| |
6.00 |
24.98 |
6.56 |
3.00 |
1.72 |
1.12 |
0.79 |
0.58 |
0.45 |
0.36 |
0.29 |
1.20 |
0.33 |
| |
6.50 |
29.15 |
7.65 |
3.50 |
2.01 |
1.31 |
0.92 |
0.68 |
0.53 |
0.42 |
0.34 |
1.40 |
0.37 |
| |
7.00 |
33.64 |
8.83 |
4.04 |
2.32 |
1.51 |
1.06 |
0.79 |
0.61 |
0.48 |
0.40 |
1.50 |
0.42 |
| |
7.50 |
38.43 |
10.08 |
4.61 |
2.65 |
1.72 |
1.21 |
0.90 |
0.69 |
0.55 |
0.45 |
1.80 |
0.50 |
| |
8.00 |
43.52 |
11.42 |
5.22 |
3.00 |
1.95 |
1.37 |
1.02 |
0.79 |
0.63 |
0.51 |
1.90 |
0.56 |
Example #2
Model Type R
Pressure Drop: Same End
RADIATOR PRESSURE DROP - FOOT OF HEAD PER RADIATOR

| |
RADIATOR MODEL
NUMBER OF TUBES
FOR FLOW |
CONNECTION PD
PER CONNECTION |
|
STD
PRESSURE
TUBE |
R-2 |
R-4 |
R-6 |
R-8 |
R-10 |
R-12 |
R-14 |
R-16 |
R-18 |
R-20 |
1/2"
CONN
PD |
3/4"
CONN
PD |
|
R-3 |
R-5 |
R-7 |
R-9 |
R-11 |
R-13 |
R-15 |
R-17 |
R-19 |
R-21 |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
4 |
4 |
5 |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| → |
0.50 |
0.21 |
0.05 |
0.02 |
0.01 |
0.01 |
0.01 |
0.00 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
| |
0.75 |
0.45 |
0.12 |
0.05 |
0.03 |
0.02 |
0.01 |
0.01 |
0.03 |
0.03 |
0.02 |
0.03 |
0.01 |
| |
1.00 |
0.79 |
0.21 |
0.09 |
0.05 |
0.04 |
0.02 |
0.02 |
0.05 |
0.05 |
0.04 |
0.04 |
0.03 |
| |
1.50 |
1.72 |
0.45 |
0.21 |
0.12 |
0.08 |
0.05 |
0.04 |
0.12 |
0.12 |
0.08 |
0.09 |
0.04 |
| |
2.00 |
3.00 |
0.79 |
0.36 |
0.21 |
0.13 |
0.09 |
0.07 |
0.21 |
0.21 |
0.13 |
0.18 |
0.06 |
| |
2.50 |
4.61 |
1.21 |
0.55 |
0.32 |
0.21 |
0.15 |
0.11 |
0.32 |
0.32 |
0.21 |
0.25 |
0.08 |
| |
3.00 |
6.56 |
1.72 |
0.79 |
0.45 |
0.29 |
0.21 |
0.15 |
0.45 |
0.45 |
0.29 |
0.35 |
0.10 |
| |
3.50 |
8.83 |
2.32 |
1.06 |
0.61 |
0.40 |
0.28 |
0.21 |
0.61 |
0.61 |
0.40 |
0.44 |
0.15 |
|
GPM |
4.00 |
11.42 |
3.00 |
1.37 |
0.79 |
0.51 |
0.36 |
0.27 |
0.79 |
0.79 |
0.51 |
0.56 |
0.18 |
| |
4.50 |
14.34 |
3.76 |
1.72 |
0.99 |
0.64 |
0.45 |
0.34 |
0.99 |
0.99 |
0.64 |
0.63 |
0.20 |
| |
5.00 |
17.57 |
4.61 |
2.11 |
1.21 |
0.79 |
0.55 |
0.41 |
1.21 |
1.21 |
0.79 |
0.80 |
0.25 |
| |
5.50 |
21.12 |
5.54 |
2.53 |
1.45 |
0.95 |
0.67 |
0.49 |
1.45 |
1.45 |
0.95 |
1.00 |
0.28 |
| |
6.00 |
24.98 |
6.56 |
3.00 |
1.72 |
1.12 |
0.79 |
0.58 |
1.72 |
1.72 |
1.12 |
1.20 |
0.33 |
| |
6.50 |
29.15 |
7.65 |
3.50 |
2.01 |
1.31 |
0.92 |
0.68 |
2.01 |
2.01 |
1.31 |
1.40 |
0.37 |
| |
7.00 |
33.64 |
8.83 |
4.04 |
2.32 |
1.51 |
1.06 |
0.79 |
2.32 |
2.32 |
1.51 |
1.60 |
0.42 |
| |
7.50 |
38.43 |
10.08 |
4.61 |
2.65 |
1.72 |
1.21 |
0.90 |
2.65 |
2.65 |
1.72 |
1.80 |
0.50 |
| |
8.00 |
43.52 |
11.42 |
5.22 |
3.00 |
1.95 |
1.37 |
1.02 |
3.00 |
3.00 |
1.95 |
1.90 |
0.56 |
Example #3
Model Type RF
Pressure Drop: Opposite End
RADIATOR PRESSURE DROP - FOOT OF HEAD PER RADIATOR

| |
RADIATOR MODEL
NUMBER OF TUBES
FOR FLOW |
CONNECTION PD
PER CONNECTION |
|
STD
PRESSURE
TUBE |
RF-1 |
RF-2 |
RF-3 |
RF-4 |
RF-5 |
RF-6 |
RF-7 |
RF-8 |
RF-9 |
RF-10 |
1/2"
CONN
PD |
3/4"
CONN
PD |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
0.05 |
0.21 |
0.05 |
0.02 |
0.01 |
0.01 |
0.01 |
0.00 |
0.00 |
0.00 |
0.00 |
0.01 |
0.01 |
| |
0.75 |
0.45 |
0.12 |
0.05 |
0.03 |
0.02 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
0.03 |
0.01 |
| |
1.00 |
0.79 |
0.21 |
0.09 |
0.05 |
0.04 |
0.02 |
0.02 |
0.01 |
0.01 |
0.01 |
0.04 |
0.03 |
| |
1.50 |
1.72 |
0.45 |
0.21 |
0.12 |
0.08 |
0.05 |
0.04 |
0.03 |
0.02 |
0.02 |
0.09 |
0.04 |
| |
2.00 |
3.00 |
0.79 |
0.36 |
0.21 |
0.13 |
0.09 |
0.07 |
0.05 |
0.04 |
0.04 |
0.18 |
0.06 |
| → |
2.50 |
4.61 |
1.21 |
0.55 |
0.32 |
0.21 |
0.15 |
0.11 |
0.08 |
0.07 |
0.05 |
0.25 |
0.08 |
| |
3.00 |
6.56 |
1.72 |
0.79 |
0.45 |
0.29 |
0.21 |
0.15 |
0.12 |
0.09 |
0.08 |
0.35 |
0.10 |
| |
3.50 |
8.83 |
2.32 |
1.06 |
0.61 |
0.40 |
0.28 |
0.21 |
0.16 |
0.13 |
0.10 |
0.44 |
0.15 |
|
GPM |
4.00 |
11.42 |
3.00 |
1.37 |
0.79 |
0.51 |
0.36 |
0.27 |
0.21 |
0.16 |
0.13 |
0.56 |
0.18 |
| |
4.50 |
14.34 |
3.76 |
1.72 |
0.99 |
0.64 |
0.45 |
0.34 |
0.26 |
0.21 |
0.17 |
0.63 |
0.20 |
| |
5.00 |
17.57 |
4.61 |
2.11 |
1.21 |
0.79 |
0.55 |
0.41 |
0.32 |
0.25 |
0.21 |
0.80 |
0.25 |
| |
5.50 |
31.12 |
5.54 |
2.53 |
1.45 |
0.95 |
0.67 |
0.49 |
0.38 |
0.30 |
0.25 |
1.00 |
0.28 |
| |
6.00 |
24.98 |
6.56 |
3.00 |
1.72 |
1.12 |
0.79 |
0.58 |
0.45 |
0.36 |
0.29 |
1.20 |
0.33 |
| |
6.50 |
29.15 |
7.65 |
3.50 |
2.01 |
1.31 |
0.92 |
0.68 |
0.53 |
0.42 |
0.34 |
1.40 |
0.37 |
| |
7.00 |
33.64 |
8.83 |
4.04 |
2.32 |
1.51 |
1.06 |
0.79 |
0.61 |
0.48 |
0.40 |
1.60 |
0.42 |
| |
7.50 |
38.43 |
10.08 |
4.61 |
2.65 |
1.72 |
1.21 |
0.90 |
0.69 |
0.55 |
0.45 |
1.80 |
0.50 |
| |
8.00 |
43.52 |
11.42 |
5.22 |
3.00 |
1.95 |
1.37 |
1.02 |
0.79 |
0.63 |
0.51 |
1.90 |
0.56 |
Example #4
Model Type RF
Pressure Drop: Same End
RADIATOR PRESSURE DROP - FOOT OF HEAD PER RADIATOR

| |
RADIATOR MODEL
NUMBER OF TUBES
FOR FLOW |
CONNECTION PD
PER CONNECTION |
|
STD
PRESSURE
TUBE |
RF-2 |
RF-3 |
RF-4 |
RF-5 |
RF-6 |
RF-7 |
RF-8 |
RF-9 |
RF-10 |
1/2"
CONN
PD |
3/4"
CONN
PD |
|
1 |
1 |
2 |
2 |
3 |
3 |
4 |
4 |
5 |
| |
|
|
|
|
|
|
|
|
|
|
|
|
| |
0.50 |
0.21 |
0.21 |
0.05 |
0.05 |
0.02 |
0.02 |
0.01 |
0.01 |
0.01 |
0.01 |
0.01 |
| |
0.75 |
0.45 |
0.45 |
0.12 |
0.12 |
0.05 |
0.05 |
0.03 |
0.03 |
0.02 |
0.03 |
0.01 |
| |
1.00 |
0.79 |
0.79 |
0.21 |
0.21 |
0.09 |
0.09 |
0.05 |
0.05 |
0.04 |
0.04 |
0.03 |
| |
1.50 |
1.72 |
1.72 |
0.45 |
0.45 |
0.21 |
0.21 |
0.12 |
0.12 |
0.08 |
0.09 |
0.04 |
| |
2.00 |
3.00 |
3.00 |
0.79 |
0.79 |
0.36 |
0.36 |
0.21 |
0.21 |
0.13 |
0.18 |
0.06 |
|
→ |
2.50 |
4.61 |
4.61 |
1.21 |
1.21 |
0.55 |
0.55 |
0.32 |
0.32 |
0.21 |
0.25 |
0.08 |
| |
3.00 |
6.56 |
6.56 |
1.72 |
1.72 |
0.79 |
0.79 |
0.45 |
0.45 |
0.29 |
0.35 |
0.10 |
| |
3.50 |
8.83 |
8.83 |
2.32 |
2.32 |
1.06 |
1.06 |
0.61 |
0.61 |
0.40 |
0.44 |
0.15 |
| GPM |
4.00 |
11.42 |
11.42 |
3.00 |
3.00 |
1.37 |
1.37 |
0.79 |
0.79 |
0.51 |
0.56 |
0.18 |
| |
4.50 |
14.34 |
14.34 |
3.76 |
3.76 |
1.72 |
1.72 |
0.99 |
0.99 |
0.64 |
0.63 |
0.20 |
| |
5.00 |
17.57 |
17.57 |
4.61 |
4.61 |
2.11 |
2.11 |
1.21 |
1.21 |
0.79 |
0.80 |
0.26 |
| |
5.50 |
21.12 |
21.12 |
5.54 |
5.54 |
2.53 |
2.53 |
1.45 |
1.45 |
0.95 |
1.00 |
0.28 |
| |
6.00 |
24.98 |
24.98 |
6.56 |
6.56 |
3.00 |
3.00 |
1.72 |
1.72 |
1.12 |
1.20 |
0.33 |
| |
6.50 |
29.15 |
29.15 |
7.65 |
7.65 |
3.50 |
3.50 |
2.01 |
2.01 |
1.31 |
1.40 |
0.37 |
| |
7.00 |
33.64 |
33.64 |
8.83 |
8.83 |
4.04 |
4.04 |
2.32 |
2.32 |
1.51 |
1.60 |
0.42 |
| |
7.50 |
38.43 |
38.43 |
10.08 |
10.08 |
4.61 |
4.61 |
2.65 |
2.65 |
1.72 |
1.80 |
0.50 |
| |
8.00 |
43.52 |
43.52 |
11.42 |
11.42 |
5.22 |
5.22 |
3.00 |
3.00 |
1.95 |
1.90 |
0.56 |
|