Model Type R2F
BTUH/ft Ratings


R2F-3 with Both Side &
Vertical Connections - Shown for Example Only
Technical
Data For All R2F Models Is Included Below
MODEL
TYPE |
HEIGHT
H |
BTUH/FT OUTPUT
@ LISTED AWT & 65°F EAT |
DRY WT
lbs/ft |
|
215°F |
190 |
180 |
170 |
160 |
150 |
140 |
130 |
120 |
| |
|
|
|
|
|
|
|
|
|
|
|
| R2F-1 |
2-3/4" |
979 |
769 |
689 |
612 |
537 |
465 |
395 |
327 |
263 |
3.6 |
| R2F-2 |
5-3/4" |
1589 |
1247 |
1118 |
993 |
872 |
754 |
640 |
531 |
427 |
6.9 |
| R2F-3 |
8-5/8" |
2019 |
1584 |
1421 |
1261 |
1108 |
958 |
813 |
675 |
542 |
10.1 |
| R2F-4 |
11-1/2" |
2417 |
1897 |
1701 |
1510 |
1326 |
1147 |
974 |
808 |
649 |
13.9 |
| R2F-5 |
14-3/8" |
3094 |
2498 |
2177 |
1933 |
1697 |
1457 |
1246 |
1034 |
831 |
16.8 |
| R2F-6 |
17-1/4" |
3470 |
2723 |
2443 |
2168 |
1904 |
1646 |
1398 |
1160 |
932 |
20.0 |
| R2F-7 |
20-1/4" |
3846 |
3018 |
2707 |
2403 |
2110 |
1824 |
1549 |
1286 |
1033 |
23.5 |
| R2F-8 |
23-1/8" |
4211 |
3304 |
2963 |
2631 |
2310 |
1997 |
1696 |
1408 |
1131 |
27.6 |
| R2F-9 |
26-1/8" |
4432 |
3478 |
3119 |
2769 |
2431 |
2102 |
1785 |
1481 |
1190 |
29.9 |
| R2F-10 |
29" |
4644 |
3645 |
3269 |
2901 |
2548 |
2203 |
1871 |
1552 |
1247 |
32.1 |
NOTE: Heat Outputs for
various AWT's include 15% Heat Effect for placement along
outside walls. Use the 215° F Output Rating with the
Correction Factor for more specific design conditions. Medium
Pressure increases Dry Weight by 10%, High Pressure increases
Dry Weight by 15%
|