Model Type R3F
BTUH/ft Ratings


R3F-3 with Both Side & Vertical Connections - Shown for Example Only

Technical Data For All R3F Models Is Included Below

MODEL
TYPE
HEIGHT
H
BTUH/FT OUTPUT @ LISTED AWT & 65F EAT DRY WT
lbs/ft
215F 190 180 170 160 150 140 130 120
                       
R3F-1 2-3/4" 1299 1020 914 812 713 616 523 434 349 4.3
R3F-2 5-3/4" 2014 1581 1418 1258 1105 955 811 673 541 8.0
R3F-3 8-5/8" 2572 2018 1810 1607 1411 1220 1036 860 691 11.7
R3F-4 11-1/2" 3082 2418 2169 1925 1690 1462 1241 1030 828 16.4
R3F-5 14-3/8" 3788 2973 2666 2367 2078 1797 1526 1266 1017 19.6
R3F-6 17-1/4" 4263 3345 3000 2663 2338 2022 1717 1425 1145 23.2
R3F-7 20-1/4" 4738 3718 3335 2960 2599 2247 1909 1584 1273 27.4
R3F-8 23-1/8" 5200 4080 3660 3248 2852 2466 2095 1738 1396 32.5
R3F-9 26-1/8" 5451 4278 3836 3405 2990 2585 2196 1822 1464 34.7
R3F-10 29" 5691 4466 4005 3556 3122 2699 2293 1902 1528 36.9

NOTE: Heat Outputs for various AWT's include 15% Heat Effect for placement along outside walls. Use the 215 F Output Rating with the Correction Factor for more specific design conditions. Medium Pressure increases Dry Weight by 10%, High Pressure increases Dry Weight by 15%
 

Runtal North America, Inc. |  187 Neck Road, PO Box 8278 |  Ward Hill, MA 01835 |  1-800-526-2621 |  Canada: 1-888-829-4901 |  Fax 1-978-372-7140