Residential Baseboard
& Wall Panels: UF Series
-
In Stock:
Take your order To Go
-
Easy to Buy:
Tell your wholesaler you want Runtal Baseboard or Wallpanels
(theyre white): The other 9 standard colors take 2 weeks to
manufacture. In Baseboard choose a height (6, 9, 12) and
a length (2-14). In Wallpanels choose a height (18, 24)
in a 2, 3 or 4 lengths. Its that easy, and you can now
take it with you!
-
Easy to
Install: Uniform fittings allow each radiator to be
piped eight different ways. Continuous Mounting eliminates
the need for backing. Simply wall mount (hardware included).
All pipe fittings are 1/2 NPT with 1/8 NPT Vent Fittings
(Manual Vent Included!). Standard Pipe Covers are also in
stock.
-
Easy to Sell:
Whether its a one radiator renovation, or a whole house,
using Runtal will impress your customer. Runtal is
attractive, durable, healthy, and comfortable. Runtal may be
used as a direct replacement for fin-tube or cast iron
baseboard (see tips on installation), or it may be used with
water temperatures as low as 140° F, (making it a perfect
radiant alternative or complement to floor heating). Runtal
Radiators carry a 5-year warranty.
|
2 ft. |
1,200 |
1,540 |
1,860 |
2,860 |
3,620 |
|
2.5 ft |
1,500 |
1,925 |
2,325 |
|
|
|
3 ft. |
1,800 |
2,310 |
2,790 |
4,290 |
5,430 |
|
3.5 ft |
2,100 |
2,695 |
3,255 |
|
|
|
4 ft. |
2,400 |
3,080 |
3,720 |
5,720 |
7,240 |
|
5 ft. |
3,000 |
3,850 |
4,650 |
|
|
|
6 ft. |
3,600 |
4,620 |
5,580 |
|
|
|
7 ft. |
4,200 |
5,390 |
6,510 |
|
|
|
8 ft. |
4,800 |
6,160 |
7,440 |
|
|
|
9 ft. |
5,400 |
6,930 |
8,370 |
|
|
|
10 ft. |
6,000 |
7,700 |
9,300 |
|
|
|
11 ft. |
6,600 |
8,470 |
10,230 |
|
|
|
12 ft. |
7,200 |
9,240 |
11,160 |
|
|
|
13 ft. |
7,800 |
10,010 |
12,090 |
|
|
|
14 ft. |
8,400 |
10,780 |
13,020 |
|
|
Installation Tips for Runtal Baseboard/Wallpanels
|
Roughing In: The rough in dimensions are the same
for all 5 heights. |
|

< Click On Image To Enlarge > |
Tips:
-
Always plan to pipe directly into the
radiator. U shapes should be avoided.
Always check your piping scheme in advance
to be sure of clearance from joists, etc.
|
|
Mounting: The mounting system is identical on
all 5 heights. |
 |
Tips:
-
Use all of the K-12 brackets provided
with each radiator.
-
Place 1 bracket 6 in from each end, and
equally space the rest.
-
Mount bracket on studs whenever possible
(use appropriate method for non-stud
mounting).
-
Mount radiators 3 from the floor for
optimum efficiency, ease of vacuuming,
and proper trim cover fit. However a
minimum of 1 between radiator and
finished floor is permissible.
-
Be sure to install leveling bolt (K-45)
prior to piping radiator.
|
|
Piping: Each radiator may be piped eight
different ways.
This should allow for the most efficient and
most attractive installation. |
 |
Tips:
-
Piping should be kept to a minimum
and should be planned to match the
standard trims.
-
Always install the air vent
(included) opposite the supply side
of the radiator.
-
Be sure to properly seal the flush
plugs (included) in the unused
fittings (3/8 and 3/16 hex
wrenches required).
-
Be sure to leave room for piping
inside corners. You will need two to
three inches plus working room,
minimum.
|
|
Trim Covers: There are 2 types
of standard trim covers:
Vertical Covers and Horizontal
Covers.
Please refer to Runtals
Radiator Trim Sheet for
complete information. |
|

Vertical Covers |
Vertical Covers:
These come standard in 3
and 10 heights and are
designed to cover straight
vertical pipe between the
radiator and the floor. They
can be easily field cut for
heights other than 3 and
10.
Horizontal Covers:
Standard trims simply snap
into place. Straight Trims
(used as End Trims & Center
Trims) are 12 long. Inside
Corners are 12 x 12 and
End Cap Trims are either 6
x 2 (right hand) or 2 x 6
(left hand). Outside Corner
Trims and other special
trims are readily available
on request.
 
Horizontal Covers |
Tips:
-
Horizontal trims require
a minimum of 2 overlap
on the radiator for
proper fit.
-
It may be easier to
purchase trims after the
radiators are installed,
but care should be taken
to ensure that all
piping has been done
with standard trim
configurations in mind.
-
If you are unable to use
standard trims on an
installation, please
call for custom trim
options.
|
|
System: Runtal will work
well in both High and Low
temperature closed loop
systems. |
Tips:
-
Always test the
system with air at a
maximum pressure of
50 PSI prior to wet
testing.
-
Runtal baseboard may
be used with
fin-tube, but the
fin-tube will
perform better if
the Runtal is at the
end of the loop.
-
Runtal is compatible
with cast iron
baseboard and cast
iron radiators.
-
In series
installation: an
individual loop
should not exceed
30,000 Btuh or 7
radiators.
|

|